Quantity
|
Total
|
||
|
|
|||
|
|
|||
Legrand TRIMOD MCS — is a three-phase modular online double-conversion UPS (VFI-SS-111) designed for critical applications, including banking, healthcare, telecommunications, and industrial automation. Its architecture provides fully independent modules with a capacity of 5-10 kVA, which can be combined up to 60 kVA with N+X redundancy. The uniqueness of TRIMOD MCS lies in its high flexibility, fast hot swapping of modules, and optimized energy consumption. Full diagnostics of this system are critical to ensure its continuous operation and maintain a high level of reliability.
What diagnostics include
Inspection / audit
- Inventory of active and redundant modules, verification of N+X configuration.
- Assessment of the physical condition of the housing, cabinet, interface connectors and access panels.
- Monitoring of installation, connection of input/output lines, grounding.
- Analysis of temperature conditions, ventilation, presence of contaminants in the ventilation holes.
Electrical tests
- Measurement of input voltage parameters on three phases: symmetry, frequency, stability.
- Output voltage control: accuracy, waveform, regulation quality with alternating load.
- Testing the response to switching between inverter, grid and bypass.
- Evaluation of power factor, harmonic levels (THDi, THDu) and system efficiency.
Inverter / rectifier / bypass test
- Functional test of each module: inverter, rectifier, DC/AC converter.
- Monitoring the operation of the static bypass: switching, protection, synchronization with the grid.
- Reading event logs: emergency trips, overloads, warnings.
- Checking the interaction between modules, including backup ones.
Battery (battery system)
- Overview of battery connections: battery type, availability, ventilation.
- Measuring voltage for each block, currents charging/discharging, internal resistance.
- Charging mode control: Float, Boost, charge uniformity analysis.
- Possibility of autonomous power supply test (upon agreement).
Cooling
- Checking fans on all modules: operability, noise, wear.
- Temperature control of power components: inverter modules, rectifiers, battery packs.
- Analysis of ventilation flow, contamination of filters or cooling channels.
Communications / monitoring
- Testing the local display and control panel: clarity of indication, navigation, messages.
- Checking network interfaces: SNMP, RS-485, Modbus TCP/RTU, Dry Contact (optional).
- Integration with centralized BMS or SCADA (if available).
Technical report
- Documentation of parameters of all modules, battery measurements, event logs and warnings.
- Identification of potentially defective or worn elements.
- Recommendations for replacing modules, batteries or fans, updating software.
When diagnostics are needed
- At least once a year — according to the regulations for modular systems.
- After installing a new module or changing the backup configuration.
- In the event of errors or failures in one of the modules, messages on the display or reduced autonomy.
- After a long downtime or switching to standby mode.
Why choose Total-Energo LLC
- Over 10 years of experience in diagnosing modular UPSs in critical industries.
- Testing at the level of each module separately with recording the results in the service database.
- The possibility of diagnostics without stopping the power supply if there is a service bypass or backup modules.
- Full reporting, technical support and recommendations for modernization or service.